Configuration of NR PCS-978S Transformer Relay and testing the following functions to ensure that the relay will operate properly as per relay settings required: 1. Transformer Differential (87T) which includes: - Pickup and Dropoff on every sides of Transformer - Timing test of Biased and Instantaneous Differential - Stability test to check if the magnitude and angle compensation are properly set on the relay as per Power Transformer nameplate (Dy1) - Testing the blocking of harmonics and CTS for Biased Differential (No blocking must be apply for Instantaneous Differential) - Slope Test 2. Other protection functions enabled such as: - Restricted Earth Fault (64REF) - OverExcitation V/f (24) - Inverse Time Phase Overcurrent on each sides of Transformer (51P) - Inverse Time Ground Overcurrent for Low Side of Transformer (51G) #ProtectionRelay #ProtectionAndControl #TestingAndCommissioning #powersystem