BLIIoT IoT Gateway BL110 Application 42-Add LAN Port Device Cellular IoT RTU Gateway S475
Add LAN Port Device Cellular IoT RTU Gateway S475
Note: if LAN port IP is changed and LAN port device auto retrieves IP, please click Write Configuration, power off gateway and power it on again. Then IP change can be viewed
4. Device Port: input LAN port device port. For example, S475 Modbus TCP port is 502. Thus put 502
5. Device Brand: Modbus; Device Model: Modbus TCP
(BL110 collects S475 through LAN port through Modbus TCP protocol)
6. The polling interval and timeout in the button can be defaulted and filled in according to requirements.
7. Select Data Type. For example, S475 power source and temperature & humidity data is 16-bit AB type, 32-bit data is not collected. Thus select 16-bit AB type and keep 32-bit data type with default setting
8. Write function code: choose 15/16, and choose according to the function code supported by the device.
Recommended by LinkedIn
9. Click OK to confirm the setting
Note: S475 device icon will appear after confirming the configuration. If more devices to be added, perform the same procedure as Step 1-9
Note: Click Write Configuration and gateway will restart automatically. After restarting, device S475 is added successfully
Add LAN Port Device Cellular IoT RTU Gateway S475 Datapoint
Note: After confirming the configuration, datapoints will appear in the box like above picture. To add more datapoints, right click the box and click Add to enter configuration box. Perform the same procedure as Step 2-14
Note: Click Write Configuration. Gateway will restart automatically. After device restarting, S475 datapoint is added successfully