Double-Beam Hanger Assemblies: Necessity, Options, and Installation Best Practices

Double-Beam Hanger Assemblies: Necessity, Options, and Installation Best Practices

Increasing load demands from technological advancement in modern mass timber construction and potential evolving building functions may warrant the need of double-beam hanger assemblies. This article explores the necessity, available options, and installation best practices for double-beam hanger systems, focusing on two popular types we supply at MTC Solutions—RICON S VS and MEGANT.


Approximately a 7-minute read.


Necessity for Double-Beam Hanger Systems

Recent technological progress has enabled the increased adoption of longer-span (≥ 30 ft) cross-laminated and glued-laminated timber framing systems in mass timber structures, aligning with the industry’s pursuit of maximizing usable floor space. The resulting intensified beam-end reactions may surpass the capacity of single pre-engineered beam hangers readily available in the market, prompting consideration of a double configuration. This could also contribute to future-proofing buildings against rising load demands due to potential functional repurposing.


RICON S VS or MEGANT?

MTC Solutions offers a range of beam hangers, with RICON S VS and MEGANT standing out as popular choices. The selection of these connectors for specific projects depends on various design factors, such as beam dimensions and anticipated loads. For design guidance, refer to our Beam Hangers Design Guide.

Figure 1. Idealized load-displacement curves of shear and inclined screws

The distinctive designs of these two types of connectors result in different load transfer mechanisms. RICON S VS employs shear screws (installed at a 90° angle) that deform gradually with the load, as shown in Figure 1, leading to a more ductile and forgiving behavior that accommodates tolerance errors within certain boundary conditions. This proves advantageous for a double configuration, allowing the initially higher connector to adjust to the level of the lower connector and thus facilitating load sharing. However, precision remains crucial, and ductility should not be misconstrued as a justification for imprecision.

In contrast, the stiffer axially loaded inclined screws (installed at a 45° angle) of MEGANT—evident in a notably steeper slope and minimal deformation before reaching capacity in Figure 1—prevent adjustments. Achieving even load sharing in a dual assembly therefore becomes unattainable in cases of initial height variations during installation. Consequently, special attention must be given during installation to ensure height precision, with a tolerance of less than 1/16”.


Best Practices for Installing RICON S VS and MEGANT in a Double Configuration

RICON S VS

Figure 2. Installation procedure for a double-RICON S VS assembly

  1. Secure a T-shaped jig to the beam end (or column), aligning both the notches at its blade’s end and in its stock—positioned on its axis of symmetry—with the relevant line of centroid of the wood member for leveling and centering.
  2. Place a RICON S VS connector against one side of the blade and atop the stock.
  3. Install a standard 3 1/8” [80 mm]-long partially threaded framing screw with a countersunk head as a setting screw into the bottom right setting-screw hole of the connector.
  4. Insert a second setting screw into the top left setting-screw hole.
  5. Install load-transferring screws row by row, either from top to bottom or from bottom to top. This sequential approach ensures that no tension is generated during installation.
  6. Repeat Steps 2–5 to install a second RICON S VS connector on the opposite side of the blade.
  7. Remove the jig.

The T-shaped jig, which can be fashioned from metal or even plywood, is a useful tool for simultaneously leveling and plumbing the connectors. The width of its blade can be customized based on the desired distance between the two connectors.

The preference for using small framing screws as setting screws over the specified connector screws to secure the beam hangers comes from their smaller and more precise nature. This choice becomes particularly crucial during end-grain installation, where it serves to minimize the risk of deviation as the screw encounters the late- and earlywood layers.

MEGANT

Figure 3. Installation procedure for a double-MEGANT assembly

  1. Level and secure a T-shaped jig to the beam end (or column) using the same approach as for RICON S VS.
  2. Place a MEGANT connector against one side of the blade and atop the stock.
  3. Install a standard 5/16” [8 mm] × 6 1/4” [160 mm] ASSY VG CSK screw as a setting screw into the bottom right hole of the connector. It is recommended to predrill both holes for setting and load-bearing screws to a depth of at least 1/2” [12 mm] with the MTC Solutions Pre-drilling Jig for enhanced installation precision.
  4. Insert a second setting screw into the top left hole.
  5. Insert 5/16” [8 mm] × 6 1/4” [160 mm] ASSY VG CSK screws as structural load-bearing screws row by row, either from top to bottom or from bottom to top. This sequential approach similarly ensures tension-free installation.
  6. Repeat Steps 2–5 to install a second MEGANT connector on the opposite side of the blade of the T-shaped jig.
  7. Remove the T-shaped jig.

Unlike the RICON S VS connector with holes for both setting and load-bearing screws angled at 90°, the MEGANT connector features holes angled at 90° in the top and bottom rows and holes angled at 45° in between. The choice of ASSY VG CSK screws over framing screws as setting screws is determined based on their greater capacity to hold the connector in place during the installation of inclined load-bearing screws. Inclined screws have the tendency to generate a lateral force during installation, pushing the connector up (or down). Framing screws are unlikely to resist such force, resulting in displacement of the connector.



For a comprehensive explanation of the installation processes for the RICON and MEGANT beam hangers, watch the following videos:


Double-beam hanger assemblies may prove essential to satisfy the ever-increasing load demands and future-proof mass timber buildings. For more information and design guidance, contact our Technical Support Team. 🙂


Franco Piva

Director at Ergodomus | 20+ Years in Mass Timber & DfMA(d) | Passionate About Woodworking | 木結構顧問

10mo

We've engineered (structural analysis and production drawings) one of the largest mass timber buildings in Europe using thousands of Megant/Ricon. We had to deepen a lot our knowledge of the products but we learned the big advantages offered by this technology. I'll be visiting the MTC in Portland and I'll be happy to stop by your booth. Ergodomus Timber Engineering

Keith Porter

P.Eng. Design Engineer at Fast + Epp

10mo

I've used a double Megant (550) before. It took care of the loads, looked great in the finished state, and the installers used a jig to ensure the hangers were installed at the correct depth in both members. Great article!

To view or add a comment, sign in