#Subtleties Inside Simulation
- Someone may think is just a simple simulation but during simulation, you will notice or discover you are doing other types of phenomena simulation required.
- As we can see in this post for point-on wave simulation, will notice other phenomena like ferro-resonance, and zero-missing.
- Thus, this post is called Subtleties Inside Simulation.
- In certain cases, surge arresters are not suitable mitigation method to avoid slow front over-voltage SFO or switching over-voltage SOV.
- Point of wave switching eliminates any transient over-voltage at the line remote end, in terms of equipment aging point of view.
- Once phase-A switched at 0.2 sec, phase-B switched 120 deg as phase shift.
- In terms of time, 120 deg in a 60Hz system is 5.3ms {0.2+0.0053}
- As the upstream circuit breaker operates in single-pole operation for POW switching, engineering judgment for ferro-resonance observation is required to avoid reactor saturation.
- Also, you can notice zero-missing phenomena in the reactor current due to a compensation ratio of more than 50%.
#Subtleties Inside Simulation#PointOnWaveSwtiching#POW#PSCAD#Ferro-resonance#Zero-missing