Ventilation Control for COVID-19 & Beyond

Ventilation Control for COVID-19 & Beyond

Darryl DeAngelis, LEED AP

ABSTRACT

The coronavirus disease 2019 (COVID-19) pandemic, brought about by the severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2), is putting a new focus on the approach to ventilation design and operation of buildings. This is because control of ventilation above normal rates is necessary to create a safe indoor environment while protecting the building infrastructure. A safe and healthy building is dependent on dilution ventilation and maintaining proper pressurization. A building’s ventilation system during normal operation strives to achieve acceptable indoor air quality (IAQ) based on building codes. The setup and operation of ventilation systems have variances and limitations. When a ventilation system fails to provide adequate ventilation, the effects of this are not immediately known. Unless the rate of outdoor airflow is actively measured, determining under-ventilation may only come after it is too late to prevent the outcome. A building is a complex system, and it and the HVAC systems are subjected to dynamic changes. Degradation, over time, impedes the HVAC system’s capabilities. Weather and seasonal changes impact the ability to provide consistent ventilation. Proxy solutions, such as CO2 control, can provide an indication of ventilation but no definitive value. Controlling ventilation and exhaust is necessary to set building pressurization and to control indoor temperature and humidity. There are health, productivity, and increased property value benefits when creating a healthy indoor environment. In the case of combating a health crisis, monitoring and controlling ventilation are paramount. SARS-CoV-2 is recognized as an airborne virus through aerosolization. This fact has changed the dynamic from providing ventilation rates to minimizing dissatisfaction with IAQ to providing ventilation rates that dilute the concentration of virus particles in the air (1, 2, 3).

This dilution through mechanical ventilation is recognized as the primary means of virus removal for all indoor environments (1, 3, 4, 5). Monitoring and controlling actual flow rates in and out of the building is essential in ensuring dilution and pressurization, maximizing efficient operation of HVAC equipment, and creating a safe and healthy building.

BACKGROUND

Building codes and standards specify minimum ventilation rates to provide acceptable IAQ. Achieving acceptable IAQ is when 80% or more of the occupants do not express dissatisfaction and there are no significant known contaminant concentrations or an unusual source that would create a contaminant of concern (6). Acceptable IAQ is designed in accordance with the Ventilation Rate Procedure to determine the minimum outdoor air for the occupants per space use and building type (6). The rates are intended to dilute dissatisfying odors from individuals and off-gassing from furniture, components, and building materials. Some spaces within buildings have exhaust requirements (e.g. toilet rooms, kitchens, janitor closets), as they have higher concentrations of odors. Buildings that are designed for laboratory or patient care use do not fall under this procedure, as they have a higher level of ventilation and exhaust design requirements and operational controls to limit the migration of infectious diseases or harmful contaminants. When buildings outdoor air ventilation systems are designed for commercial buildings, they are typically engineered in accordance with the mechanical code prevailing for local jurisdiction (e.g. International Mechanical Code (IMC), Uniform Mechanical Code (UMC), California Title 24 part 6 (T24), ANSI/ASHRAE Standard 62.1 (62.1)). These codes and standards are under continuous maintenance and constantly evolving, with a new full publication every 3 years. Throughout North America, there are several published versions in effect by state, province, county, or city. The prescriptive ventilation rates within these codes are minimum requirements. Most professionals design only to these minimum rates as there is always a trade-off between ventilation and energy, although some owners choose a design that enhances ventilation by following WELL (7), LEED (8), and IGCC (9).

Ventilation rates are typically set by a Testing Adjusting Balance (TAB) professional. If a project does not enlist these services, then it typically falls on the installing contractor or, in the case of T24, an Acceptance Test Technician. If there is a Commissioning (Cx) professional on the project, they may perform functional performance tests to verify outdoor air ventilation and exhaust systems are operational. The conventional thinking is that a designed ventilation rate will be set up during construction and that this one-time setting will forever maintain the correct ventilation requirements of the building. However, certification that airflow rates meet specifications is the most difficult field measurement that a TAB engineer has to perform (10). The amount of outdoor air ventilation in an indoor environment is difficult to perceive with our senses. Unless it is directly measured, a person cannot determine if the amount of ventilation air is the correct amount. There are delayed indications of inadequate ventilation that affect humans, such as headaches, fatigue, and upper respiratory irritations. When this happens to a large percentage of building occupants, it is termed sick building syndrome (SBS) (11).

When the ventilation setpoint is made, it is typically adjusted to deliver the ventilation rate designed for full occupancy at full flow with all zones proportionally balanced (10, 12, 13). Sections 5.1 and 5.3 of 62.1 require the minimum ventilation airflow to be maintained and delivered under any load condition or dynamic reset condition and provided with controls that maintain no less than the outdoor air intake flow as required by the prescriptive ventilation procedure (6). The 62.1 User’s Manual 14 clarifies this by stating, “To comply, most variable-air-volume (VAV) systems will need special design considerations and often features such as outdoor airflow sensors, modulating dampers, and injection fans.” It further states, “A major consideration with VAV systems is that the negative pressure behind the outdoor air intake in the mixed air plenum will typically vary with supply air volume. At low supply airflow rates, this negative pressure will decrease, and sufficient outdoor airflow may not be maintained with a fixed outdoor air intake damper position—or even if a dedicated fixed minimum air intake is used.”

With the ongoing effort to save energy in the operation of buildings, the energy codes and standards (e.g. International Energy Conservation Code (IECC), California Title 24 part 6 (T24), ANSI/ ASHRAE Standard 90.1 (90.1)) have incorporated fan airflow control on constant volume units that reduce the supply fan speed as a function of load. The effect of this change in airflow is no different than VAV. Therefore, newer constant volume systems need to address outdoor ventilation control in the same manner as VAV. Furthermore, the 62.1 User’s Manual14 addresses another problem with constant volume systems: “If the thermostat in such a system has a fan on/off/auto switch and the switch is left in the auto position, the fan will cycle off when the temperature set point is reached. If the fan system also supplies outdoor ventilation air, the cycling fan causes the outdoor air supply and ventilation to be discontinuous. Since many untrained people do not understand this, the switch is often placed in the auto position, resulting in inadequate ventilation.”

Outdoor damper curves are different for system operation at design and turndown. The amount of damper opening to maintain constant minimum is greater at turndown than design (15). Additionally, dampers and actuators have combined hysteresis, the tendency to arrive at different positions for the same signal input when moving in different directions (15). It makes the position of the actuators very inaccurate; this is especially serious concerning the minimum position of the outside air damper (16). Hysteresis is caused by internal damper linkages and low leak seals, large damper sections, actuator to damper linkages, multiple sections jack-shafted, and higher torque applications requiring “piggy backed” actuators. Actuators have signal hysteresis to protect motors and mechanical hysteresis due to internal gear trains and springs. An actuator’s feedback is believed to be a closed-loop control. However, it only provides information on the actuator position, not the actual damper position or the ventilation flow rate.

Changes in weather and seasons impact ventilation setpoints. Wind can hinder intakes or exhausts; the ventilation rate can be reduced by wind pressure (17). Wind creates pressures that affect the mixed air plenum pressure in a similar way as varying the fan speed. On systems without mixing plenums (e.g. exhaust, makeup air, Dedicated Outdoor Air Systems (DOAS)), the wind can add a pressure source in series with the fan that impacts operation on the fan curve (17). Fixed damper setpoints are affected by wind and stack pressure (18). Stack pressure, known as Stack Effect, is due to density differences in the air. This density difference is caused by temperature differences between indoor and outdoor and creates a pressure difference that changes with seasons. This pressure can act on HVAC openings and extend through return or exhaust ducts that extend multiple floors. The pressure differential is directly proportional to building height and the difference between indoor and outdoor temperatures (19). Although it is often considered a phenomenon in tall buildings, locations that have large temperature differences between summer and winter can experience a stack effect on smaller buildings as well. Thereby an effort to balance intakes and exhausts in the summer can result in reduced flow rates in the winter. This pressure also varies across the building envelope and floor to floor, making maintaining building pressurization control to prevent infiltration a dynamic problem.

Not all velocity and airflow measurement systems are equal. Some have limitations in ranges and application, are more affected by installed conditions, are dependent upon field measurements, or have wide ranges in precision (17). Since all systems have some degree of turndown, it is important to look at the complete range of operations. It is important to understand all the components that make up the flow measurement device, such as measurement limitations and potential drift, and any maintenance or calibration requirements associated with them (e.g. pressure transducers). It is best to use a measurement device that has been factory calibrated for the application and is traceable to a national airflow measurement standard such as NIST. Products that have a low-density measurement or require setup based on field measurement carry additional errors.

Demand control ventilation (DCV) is an energy saving strategy that is required by energy codes, for some high occupancy and variable load spaces. It is permitted by ventilation codes and standards as a means of Dynamic Reset. One of the more popular ways to reset the zone ventilation and/or the outdoor air ventilation rate is by sensing CO2 in the space as a proxy for occupancy count. This is because the VRP has a ventilation rate per person component. CO2 DCV has many challenges in implementation; among them is determining the correct generation rate by knowing the population makeup and activity level (20). It is important to note that CO2 is a lagging indicator, and steady-state concentrations will only be achieved if conditions, including occupancy, are constant for long periods of time. Sources of error for this strategy are the accuracy of CO2 sensors, their placement, and requiring that the air in the space is well-mixed. Too often, control strategies and some standards make incorrect assumptions in the parameters used. There is a codependent relationship between CO2 levels and ventilation rates, and it will differ for occupancy type. It is also common for controls to not increase ventilation off-floor area base rates until desired steady-state measurements (e.g., 1000 ppm) are reached. This approach saves energy; however, it causes under-ventilation by not providing the ventilation rate for the actual current population. There are improved approaches to incorporate CO2 DCV (21).

DISCUSSION

Viruses have been identified as the most common cause of infectious disease acquired within the indoor environment (22). Airborne transmission can occur via direct contact with droplets, skin flakes, and fungal spores. Aerosols can be generated (atomized) during breathing, speech, sneezing, singing, vomiting, feces evacuation, and toilet flushing (22, 23). Aerosols can be as large as 100 µm (microns) in diameter and can exist in liquid or solid form with the majority of respiratory aerosols being less than 10 microns (22, 23, 24). As a reference, the human hair is between 50 to 70 microns. A study has shown that individuals coughing while infected with influenza can release 75,000 respiratory droplets (25). The size distinction is important because larger droplets settle (fall to the floor, furniture, clothing), and smaller ones remain suspended in the air from minutes to hours (4, 22, 26).

The room environment impacts the survival of the virus and its ability to remain airborne (26). When a respiratory droplet is expelled, it is at 100% relative humidity (RH), and it decreases rapidly in size by evaporation into a room with a lower RH (27,28). This reduced size droplet has the potential to survive longer in the air and to reach different parts of the respiratory tract. Those that remain in the air may eventually become inactivated, settle out, or be diluted out by ventilation and exhaust (29). It is important to note that the virus itself is smaller in size than the respiratory droplet, so there can be more than one virus particle per respiratory droplet. As an example, SARS-CoV-2 is 0.12 microns and influenza is 0.10 microns. It is also possible for a larger droplet to settle out and then to be resuspended back into the air as a smaller droplet from clothing, the floor, or other surface that is disturbed4,6. Other viruses that can be transmitted via airborne aerosols are tuberculosis, measles, chickenpox, legionella, SARS CoV-1, and MERS-CoV (4, 5, 30).

Characteristics of viruses are unique to a virus and require significant research. Typically, a virus crisis ends before much is known about it. We have a version of Influenza on an annual basis; however, scientists still do not know all there is to know about its ability to transport and infect people (31). What we know is that the infectious concentration in the air is dependent on the generation rate (Quanta) and the removal of the virus by settling inactivation (decay rate), and ventilation (29). The Quanta is influenced by how it is atomized, droplet size, temperature, and humidity. Indoor environments are perfect for the transmission of viruses. However, we can increase the decay rate and strengthen the human response if we keep room RH between 40-60%. Viruses have more vitality or less chance of inactivation when the RH is > 90% or <40% (27, 29, 32, 33). It is also known that the amount of virus RNA copies atomized, increases with metabolic rate and vocal level (34). It is recognized that coughing and sneezing produce significant levels of atomized particles. However, in some cases, more particles are produced by singing and shouting; also, breathing and general speaking will also release virus particles (23, 35, 36).

A study of SARS-CoV-2 breath emission into the air during the early stages of COVID-19 measured up to 100,000 RNA copies per minute (37). Another study looked at the risk for infection before and after a lockdown in Italy in different retail buildings, with the post-lockdown cases limiting personnel and using PPE. It showed an infected person spending only 10 minutes inside the store, has the potential to infect another person who comes in 16 minutes after the first person leaves. The risk increases the more the individuals spend time indoors. In both pre and post-lockdown calculations, mechanical ventilation significantly lowered the risk (35). Ventilation, when implemented correctly as an engineering control, can have a significant impact on providing a safe environment.

Lack of ventilation control will create an environment that is at risk. Without adequate ventilation, the virus concentration will continue to climb and the recirculated air distribution within the indoor space can act as a super-spreader; infections go from close contact additive to sharing the same space exponential (36,38). In the case of a call center in South Korea, there was a 43.5% infection rate (94 cases), within a few days. In another case in Canada a small church social event of only a few hours, where they followed social distances and wore gloves, resulted in 58% infection rate (24 cases). It was reported that none of the attendees had traceable contact to any know infected person. It is thought that the virus was in the church air from the previous day (39).

Air moving components (e.g. fans, dampers, louvers, ducts) and heat transfer equipment (e.g. hydronic coils, DX coils, energy wheels) are typically sized to convey and condition only the minimum ventilation requirements. The ability to add additional ventilation air may be limited while maintaining comfort and energy efficiency. However, the need to provide more dilution for a safer indoor environment should outweigh the penalties.

DCV should be disabled during times that need enhanced dilution ventilation (1). Maximizing economizing by increased high limits and using integrated economizer control strategies will increase dilution air. Resetting supply and space temperatures will also assist in providing more ventilation. However, a building must be treated as if it is a system. Any change in the operation in one area can have an unexpected change someplace else. In general, buildings should be kept slightly positive to neutral. Any changes in ventilation rate must have corresponding change in exhaust rate. It is not fan pressure that creates building pressure, it is the differential of flows into and out of the building (pressurization flow) that creates and maintains pressurization (40). In more complex buildings, flow maps should be created to determine interaction of systems and ensuring intended flow paths and pressurization flow. This is common for laboratories and hospitals and should be standard practice for all multiple-zone buildings.

History has a way of repeating itself. A drive towards energy efficiency creates new challenges in building operations. After the 1970’s energy crisis, reduced ventilation and tighter buildings generated SBS and fungal growth. The push for tighter buildings, demand control ventilation, and/or the use of air cleaning technologies to limit the outdoor ventilation rates handicaps buildings to maintain a healthy indoor environment. The focus is misdirected to building operating costs and ignoring the #1 asset, the occupant. Enhanced ventilation not only protects people but also enhances their performance. Ensuring the correct amount of ventilation and exhaust is not only insurance but an investment in the health, productivity, and protection of the building and occupants (41, 42).

In another paper’s conclusion it was stated “However, the air-conditioners in current use in most buildings may be unable to use MERV-13 filters or have fans that are not able to handle the required volume of outdoor air. Indeed, a new generation of air-conditioners that meet these requirements may be needed. (38)" What is needed can be achieved today with the correct planning and integration of airflow measurement and control into buildings.

CONCLUSION

High sensor density airflow measuring devices should be incorporated at a minimum in outdoor air, supply air, return air, and exhaust air. Strong consideration should also be made to accurately measure flows to zones in DOAS and VAV systems (43). Additional airflow measuring devices may be needed to combat wind and stack effects (40). Avoid CO2 control as means to provide accurate and repeatable ventilation as it has drift, and is often misunderstood and applied. Make sure you select the correct airflow measurement device to suit the application (17).

Whether it is ensuring the minimum ventilation or integrating enhanced ventilation with new control strategies, accurate and repeatable measurement of the outdoor ventilation air is necessary to achieve the most efficient system operation. Not only will real-time airflow measurement provide the rate of flow, but this valuable data can be used to set upper and lower limits, maintain proper pressurization throughout operating conditions, perform ventilation load calculations, reset rates as conditions change, and initiate alarms.

It is a perfect time to evaluate existing HVAC systems and determine how outdoor air ventilation can be better measured and controlled. It is an easy and economical way to show your building is in compliance with codes and can meet the needs of enhanced dilution for safer indoor environments. It essentially pays for itself by bringing value to the building and occupant productivity benefits (41, 42). Some building types, such as schools, have significant research showing ventilation is a systemic problem that leads to respiratory health problems, absenteeism, developmental challenges, and building damage (44). This is not the first airborne virus and will not be the last. Act now, not only for today’s challenges but also for the future.

RESOURCES

1. ASHRAE Position Document on Infectious Aerosols – April 14, 2020

2. It is Time to Address Airborne Transmission of COVID-19 - Clinical Infectious Diseases

3. Aerosol transmission of SARS-CoV-2? Evidence, prevention, and control – Environmental International

4. How can airborne transmission of COVID-19 indoors be minimized - Environmental International

5. Recognizing and controlling airborne transmission of SARS CoV-2 in indoor environments – Wiley

6. ANSI/ASHRAE Standard 62.1-2019 Ventilation for Acceptable Indoor Air Quality

7. Well Building Standard Support in the Fight Against COVID-19 - International Well Building Institute

8. Managing Indoor Air Quality during COVID-19 – US Green Building Council

9. International Green Construction Code

10. ANSI/ASHRAE Standard 111-2008

11. Office Buildings: Health, Safety, and Environment – Springer

12. ANSI/AABC National Standard for Total System Balance 7th Ed.

13. NEBB Procedural Standard for Testing, Adjusting and Balancing of Environmental Systems 8th Ed. 2015

14. ASHRAE Standard 62.1 User’s Manual Based on ANSI/ ASHRAE Standard 62.1-2016

15. Dampers and Airflow Control – ASHRAE 2010

16. Damper Actuators Application Guide – Belimo 2019

17. 2017 ASHRAE Handbook – Fundamentals, Chapter 24.8 Wind Effect on System Operation, Chapter 37 Measurements and Instruments

18. Advanced Variable Air Volume VAV System Design Guide - Energy Design Resources 2009

19. 2019 ASHRAE Handbook – HVAC Applications, Chapter 4.1 Stack Effect

20. Carbon dioxide generation rates for building occupants – Indoor Air

21. Improve Traditional CO2-DCV with Outdoor Airflow Measurement – David Dougan

22. Droplet fate in indoor environments, or can we prevent the spread of infection? – Indoor Air

23. Size distribution and sites of origin of droplets expelled from the human respiratory tract during expiratory activities - Aerosol Science

24. FAQs on Protecting Yourself from COVID-19 Aerosol Transmission

25. Quantity and Size Distribution of Cough-Generated Aerosol Particles Produced by Influenza Patients During and After Illness – Occupational and Environmental Hygiene

26. Characterization of infectious aerosols in health care facilities: an aid to effective engineering controls and preventive strategies - American Journal of Infection Control

27. Humidity-Dependent Decay of Viruses, but Not Bacteria, in Aerosols and Droplets Follows Disinfection Kinetics – Environmental Science & Technology

28. Interaction of aerosol particles composed of protein and salts with water vapor: hygroscopic growth and microstructural rearrangement – Atmospheric Chemistry and Physics

29. Dynamics of Airborne Influenza A Viruses Indoors and Dependence on Humidity - Plos One

30. Airborne Infectious Microorganisms – Encyclopedia of Microbiology, 4th edition

31. Concentrations and size distributions of airborne influenza A viruses measured indoors at a health centre, a day-care center and on aeroplanes – Interface

32. Humidity as a non-pharmaceutical intervention for influenza A – PloS One

33. Effects of indoor environmental parameters related to building heating, ventilation, and air conditioning systems on patients’ medical outcomes – Indoor Air

34. Quantitative assessment of the risk of airborne transmission of SARS-CoV-2 infection – Environmental International

35. Estimation of airborne viral emission: Quanta emission rate of SARS-CoV-2 for infection risk assessment – Environmental International

36. Transmission of SARS-CoV-2 by inhalation of respiratory aerosol in the Skagit Valley Chorale super spreading event - MedRxiv

37. COVID-19 patients in earlier stages exhaled millions of SARS CoV-2 per hour – Clinical Infectious Diseases

38. Ventilation and the SARS-CoV-2 Coronavirus – medRxiv

39. Calgary church hopes others learn from their tragic COVID-19 experience – CTV News

40. Best practices for infiltration and building pressurization – Consulting-Specifying Engineer

41. Healthy Buildings: How Indoor Spaces Drive Performance and Productivity – Allen and Macomber – Harvard University Press

42. Ventilation Rates and Office Work Performance – LBNL IAQ Resource Bank

43. ASHRAE Design Guide for Dedicated Outdoor Air Systems (DOAS)

44. The Importance of Controlled Ventilation in Schools – Darryl DeAngelis, EBTRON

To view or add a comment, sign in

Insights from the community

Others also viewed

Explore topics