Torsional Oscillations Excited by Feeding in Subsynchronous Currents from the Grid into the Electrical Generator ()
1. Introduction
Due to the steady increase, see Figure 1, of converters and converter systems in the German transmission grid, e.g. due to the steady expansion of offshore wind
Figure 1. Increasing number of frequency converters in Germany (Source: BMWI).
farms and solar power, it is necessary to deal with the grid based excitation of torsional oscillations of the turbo sets by sub-synchronously fed-in currents. It is to be expected that there will be an increase of sub-synchronous feeding processes through frequency converters into the transmission grid in the future. These processes will then lead to subsynchronous power oscillations between the grid and the generator, which in turn may excite subsynchronous torsional natural frequencies of the turboset shaft trains. This problem is currently being investigated and discussed in Germany, e.g. within an expert committee under the leadership of the VGB PowerTech e.V. A decisive question here is the ability of frequency converters to excite or to damp torsional oscillations. For this purpose, extensive simulations, which include both grid models and turboset models, are carried out by the grid operators. The central criterion for deciding whether the turboset of a power plant could be affected by the connection of a frequency converter is the value of the “Unit Interaction Factor” (UIF).
If the value of the UIF is below 0.01, there is no risk of negative effects on the turbo set by switching on a frequency converter. The UIF itself is calculated according to [1] [2] as follows, see Equation (1):
(1)
Herein mean:
: DC nominal power of the frequency converter,
: Nominal apparent power of the generator,
: Short-circuit capacity at the DC commutation node including the generator,
: Short-circuit capacity at the DC commutation node without the generator.
2. Effect of the Feed in of Sub-Frequency Currents on the Generator Power
The starting point for the following considerations is the definitions of the currents and voltages of the SSR feed-in model according to Figure 2. Based on this model, the generator power at the terminals is first derived in a single-phase state and then extended to the three-phase state.
The currents and voltages shown in Figure 2 have the following meaning:
Single-phase stator voltage with the grid frequency
:
mit
Single-phase stator current with the grid frequency
:
mit
Sub-frequency current with the frequency
, which is fed from the grid and flows into the generator:
with
and
Due to the excited torsional oscillations, angular oscillations of the generator rotor occur with a natural torsional frequency
. This additionally induces a voltage in the stator winding, which produces a sub-frequency current with the frequency
:
with
and
The used index “1” (cause) or “2” (effect) shall only allow a differentiation
Figure 2. Basis of the SSR feed-in model.
between these two states at this point. Furthermore it was assumed that the current
opposite to the current
flows. This state occurs if the condition
is fulfilled, where
a part of the phase angle
represents. Starting from Figure 2 the single-phase power p(t) is now formed at a generator terminal e.g. of phase u:
(2)
In the following, each summand from Equation (2) is calculated individually to ensure clarity.
(3)
Equation (3) describes the mean value of the instantaneous power as a function of
and the double line frequency power oscillation.
(4)
Equation (4) contains the fluctuating power component with the frequency
, which is fed from the grid and excites the generator rotor to torsional oscillations.
(5)
Equation (5) represents the fluctuating power component, which is generated by the excited torsional oscillations of the generator rotor and fed into the grid. This process takes place with the frequency
. The addition of the terms from Equations (3)-(5) leads to the sum in Equation (6):
(6)
By feeding in subsynchronous currents, components with new frequencies in the power components are created in the single-phase total power, see Equation (6), which lie below and above the line frequency, namely, , ,. In the following, only terms with subsynchronous frequencies will be considered more closely. The excitation of a torsion natural frequency of the shaft train takes place exactly when the following condition is fulfilled:
●
◯ : excited subsynchronous torsional natural frequency of the shaft train. (7)
This is a necessary condition. In addition, the following optional condition of the system consisting of the turboset and the electrical grid shall apply:
●
◯ : existing natural grid frequency of the electrical grid. (7a)
The combination of Equation (7) with Equation (7a) then results in Equation (7b):
(7b)
From Equation (7b) it can be deduced that the currents fed into the generator from the grid occur with a sub-frequency grid natural frequency.
2.1. Extension to a Three-Phase System
The next step is the extension of the single-phase to the three-phase view under respect of the 120˚ electrical phse shift. The starting point for this is Equation (6). Under the assumption that the current and voltage amplitudes are the same in each case, which differs only by the corresponding phase angles, Equation (8) is obtained:
After transforming and reducing the equation, the final result is:
(8)
The first summand in Equation (8) stands for the stationary power component. The second summand describes the subsynchronous power oscillation, which is generated in the generator by the sub-frequency currents fed from the grid. The third summand contains the subsynchronous power oscillation, which is emitted from the generator into the grid. The damping factor α is of decisive importance here, since it determines whether the power oscillation is stationary with sub-synchronous power oscillations or whether the sub-synchronous power oscillations decay over time.
2.2. Variation in Time of the Three-Phase Power
To illustrate the effects of the power oscillations caused by the sub-frequency currents fed into the system, a corresponding scenario is shown in Figure 3 and Figure 4. Figure 3 shows the power oscillation for 500 time cycles, Figure 4 shows the same scenario for a section of 100 time cycles. Here the process of frequency modulation is clearly visible. The power oscillates with an active power of 0.7 p.u. The sub-synchronous active power fed into the generator from the 50 Hz grid is 0.05 p.u. with a frequency of 33 Hz and a damping factor of 0.003. The sub-synchronous active power fed into the 50 Hz grid from the generator is 0.04 p.u. with a frequency of 17 Hz and a damping factor of 0.002. Furthermore, a frequency of 1.0 p.u. was used, with 0.7 p.u., with 0.05 p.u. and with 0.04 p.u.
2.3. Selected Boundary Conditions for the Excitation
Taking Equation (8) into account, various excitation cases for 3-phase operation using the frequency ratios are presented below.
Figure 3. SSR power oscillation via 500 time cycles in p.u.
Figure 4. SSR power oscillation via 100 time cycles in p.u.
Case a) using Equation (7), (7a) and (7b):
(10)
From Equation (10) it can be seen that the excitation of the shaft train to torsional vibrations by feeding a sub-frequency power oscillation with a torsional natural frequency of the shaft train. Furthermore, the sub-frequency power oscillation fed into the grid oscillates with a grid natural frequency.
Case b):
(11)
The two subsynchronous summands in Equation (11) add each other with the same frequency, so that in this case there is an amplification of the subsynchronous power components up to a continuous excitation.
Case c):
(12)
The boundary condition introduced in Equation (12) leads to the fact that both the power oscillation fed subfrequently into the generator has a grid normal frequency as well as the subfrequent power oscillation fed into the grid with a grid natural frequency exists.
Case d):
(13)
Equation (13) shows that the sub-synchronous power oscillation fed into the grid under this assumption occurs with a grid natural frequency.
2.4. Evaluation of the Results
The feed in of sub-frequency currents from the grid into the generator of a conventional turboset can excite the shaft train involved to torsional oscillations, see [3] . This depends largely on the prevailing frequency conditions. The excited torsional oscillations induce synchronous generated voltages in the generator stator which in turn lead to sub-frequency currents. Each of the generated sub-frequency currents causes in turn subsynchronous power oscillations which are superimposed on each other. Whether these power oscillations remain unchanged in their effects as a function of time or decay with time depends on the damping factor.
3. Conclusion
Since several decades it is well-known that grid faults are able to excite torsional oscillations of turbo set shaft trains, see [4] [5] [6] [7] . By the implementation of an increasing number of converter systems to the grid, the exciation mechanism will change and become more complex. According to this, deeper investigations in all directions are necessary, e.g. measurements of torsional oscillations during operation ( [8] [9] ), but also theoretical simulations of the system “Grid-Converter-electrical Generator”, see [3] . In general, the interaction between the grid frequency, the natural electrical grid frequencies and the mechanical torsional natural frequencies has to be considered in a more effective way. One important question in general will be, if the well-known protection systems ( [10] ) for turbo sets are able to deal with the new grid situation without any restrictions.